Remark
The above information is available for all ebm-papst Modbus fans with interface
version >= 5.0 (2012). Depending on the type of fan, additional information is
available. The application does not read this additional information, as reading
causes malfunction on some types of fans.
Error and warning codes are shown as decimal value, for example error code ‘17’.
They must be converted into a bit string, for example ‘0000 0000 0001 0001’.
According to EBM Papst documentation, this means FB (General fan fault) and
PHA (Phase error).
When using a Modbus fan, both fans must be Modbus fans.
Engineering of communicative devices
Modbus components