Available parameters
Actual values
BACnet object
R/RW
Note
Outside air damper position
Prio 2: Fire / Smoke
Prio 5: Protection from plant control
DmpOaPos
AO,163 (A1)
AO,166 (A2)
AO,168 (A3)
AO,169 (A4)
AVAL,741 (AO1)
AVAL,745 (AO2)
RW
Outside air
damper
Mixing air damper position
Prio 2: Fire / Smoke
Prio 5: Protection from plant control
DmpMixPos
AO,162 (A1)
AO,165 (A2)
AO,167 (A3)
AO,170 (A4)
AVAL,740 (AO1)
AVAL,744 (AO2)
RW
Recirculating air
damper
Recirculating damper heating/
cooling state
MixDmpHCSta
MVAL,943
R
1: Neither
2: Heating
3: Cooling
Basic settings
BACnet object
R/RW
Note
Outside damper delay time
DlyOnAflVntReq
PINTVAL,667
RW
S
Outside damper minimum position
OADmpMin
PINTVAL,729
RW
Default 30%
Special settings
BACnet object
R/RW
Note
Damper TSu Kp
GainDmpCtr
AVAL,735
RW
%/K
Damper TSu Tn
TnDmpCtr
PINTVAL,668
RW
S
Application functionalities
Outside air dampers (DmpShoffOa11y)
5
120 | 170
A6V10733786_en_c