5.5.1.2 Available parameters for exhaust fan (linear fan speed)
Available parameters for
exhaust fan
Current state
BACnet object
R/RW
Unit
Exhaust fan speed
Prio 2: Fire / Smoke
Prio 5: Protection
FanEhSpd
A1: AO,103
A2: AO,112
A3: AO,121
A4: AO,130
Modbus: AO,150
RW
%
Exhaust fan speed feedback
FanEhSpdFb
Tacho:AI,69
0~10V:AI,97
Modbus: AI,164
R
%
Exhaust fan fault
FanEhFlt
Modbus: BI,145
R
Operating mode settings
BACnet object
R/RW
Unit
Unoccupied: exhaust
SpFanEhSpdUcd
AVAL,294
RW
%
Economy: exhaust
SpFanEhSpdEco
AVAL,293
RW
%
Comfort: exhaust
SpFanEhSpdCmf
AVAL,292
RW
%
Fire place: exhaust
SpFanEhSpdFplc
AVAL,92
RW
%
Kitchen hood: exhaust
SpFanEhSpdKtch
AVAL,528
RW
%
De-icing fan speed exhaust
SpFanEhSpdDeic
AVAL,295
RW
%
Special settings
BACnet object
R/RW
Note
Tacho signal mapping
Pulses/sec for 100% fan speed
FanSuSpdFb
AI,69
RW
Property 4965
Range 0…300 pulse/s
Testing and debugging
BACnet object
R/RW
State
Fan device mode
Prio 2: Fire / Smoke
Prio 5: Protection
FanEhDevMod
MVAL,163
RW
1: Off
2: Control mode
3: Max.air vol.flow
4: Min.air vol.flow
5: Manual speed
6: Smoke ctrl. air flow
7: De-icing air vol.flow
Application functionalities
Fan speed control
5
A6V10733786_en_c
63 | 170