Input X8
Parameter
BACnet object
Selection for X8
X8Sel,
STR_VIEW,59
Selection
BACnet object
R/W
Signal type
Range
None
-
-
-
Extract air temperature
TEx
R
NTC10k
-50…80 °C
Exhaust air temperature
TEh
R
NTC10k
-50…80 °C
Supply air temperature after heat
exchanger
TSuAfHExg
R
NTC10k
-50…80 °C
Supply air temperature after
preheating coil
TSuAfPreHcl
R
NTC10k
-50…80 °C
Flow temperature preheating coil
TFlPreHcl
R
NTC10k
-50…80 °C
Frost protection temperature for
heating coil
TFrPrtHcl
R
NTC10k
-50…80 °C
Rapid ventilation input
RpdVntIn
R
Contact
NO
Kitchen hood ventilation input
KtchVntIn
R
Contact
NO
Fireplace ventilation input
FplcVntIn
R
Contact
NO
Air filter differential pressure
monitor
FilAirDiffPMon
R
Contact
NO
Fire damper feedback
FdpFb
R
Contact
NO
Preheating coil overtemperature
detector
PreHclOvrTDet
R
Contact
NC
Heat exchanger condensation
monitor
HExgCdnMon
R
Contact
NO
Rotary heat exchanger fault
RotHExgFlt
R
Contact
NO
Heat exchanger differential
pressure monitor
HExgDiffPMon
R
Contact
NO
Heating coil overtemperature
detector
HclOvrTDet
R
Contact
NC
Cooling coil DX evaporator fault
CclDxFlt
R
Contact
NO
Emergency off
EmgOff
R
Contact
NC
Smoke extraction
Smext
R
Contact
NO
Input room operating mode comfort CmfOpModRIn
R
Contact
NO
Input room operating mode
economy
EcoOpModRIn
R
Contact
NO
Input room operating mode
unoccupied
UcdOpModRin
R
Contact
NO
Input room operating mode
protection
PrtOpModRIn
R
Contact
NO
Configuration
Configuring the hardware
4
A6V10733786_en_c
39 | 170