5.5.4 Fan speed control for temporary modes
5.5.4.1 Fan boost
The Fan boost mode can be activated as a temporary mode to temporarily
increase ventilation, e.g. after a bath or in a sauna. In this case, Fan boost is
activated directly and kept active until the set time has elapsed.
The Fan boost mode uses the fan speeds defined for the Comfort operating mode.
Fan boost is blocked if the configuration of the room influence on the fan speed is
in mode 3 or 4.
Available parameters
Current values
BACnet object
R/RW
Unit / Note
Activation input status
RpdVntIn
D1:BI,69
D2:BI,86
X3:BI,103
X8:BI,120
R
Pulse or 'egg
timer' signal
Rapid ventilation status and operation
RpdVntOp
BVAL,166
RW
Duration
TiRnRpdVnt
PINTVAL,70
RW
Min
Application functionalities
Fan speed control
5
74 | 170