Humidity controller, actuator output diagram
Available parameters
Current value
BACnet object
R/RW
Unit
Duct air humidity value
HuRelEx
X1:AI,68
X2:AI,72
X3:AI,74
X22 :AVAL,319
AI2 :AVAL,470
R
% r.H.
Room air humidity value (QMX.3 P40)
HuRelR
AI,102
R
% r.H.
Room air humidity value (QMX3. P70)
HuRelR
AI,104
R
% r.H.
r.H. setpoint
PrSpDhu
AVAL,148
R
% r.H.
Basic settings
BACnet object
R/RW
Unit
Unoccupied: r.H. setpoint
SpHuRelRUcd
AVAL,311
RW
% r.H.
Economy: r.H. setpoint
SpHuRelREco
AVAL,151
RW
% r.H.
Comfort: r.H. setpoint
SpHuRelRCmf
AVAL,149
RW
% r.H.
Special settings
BACnet object
R/RW
Unit
Dehumidification Kp
GainDhuCtr
AVAL,152
RW
% / %
r.H.
Dehumidification Tn
TnDhuCtr
PINTVAL,76
RW
s
On time for fan control
TiRnDhuCtl
PINTVAL,77
RW
s
Off time for fan control
TiIrptDhuCtl
PINTVAL,78
RW
s
Hysteresis for preheating coil and external dehumidifier
HysDhuCtr
AVAL,341
RW
% r.H.
Application functionalities
Fan humidity control (DhuCtl11y)
5
A6V10733786_en_c
81 | 170