6 Operation
6.3 Configuration of the Device
82
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
1) After the parameter changes have been enabled, the device will reset.
2) After enabling the parameter changes, any currently active Modbus TCP connections will be closed. The
Modbus TCP client must later reopen these connections.
3) After having selected IEC 61850 or changed the IEC 61850 settings, the device must be restarted.
4) The parameters stated here are only used when
yes
is selected for “
Use settings in the table below
“ (see
Figure 6-36). This allows for a simple configuration of the GOOSE publishers without using DIGSI and the
SICAM I/O Mapping Tool.
Bus Protocol IEC 61850
3)
IEC 61850 Edition
Edition 1
Edition 1
Edition 2
IED name number
4)
1
0 to 65534
Multicast MAC address
4)
[xx-xx-xx-xx-xx-xx] hexadecimal
App ID
4)
[xxxx] hexadecimal
VLAN ID
4)
[xxx] hexadecimal
VLAN priority
4)
4
0 to 7
Retransmit MIN
4)
5
1 ms to 500 ms
Retransmit MAX
4)
3000
500 ms to 65 534 ms
Table 6-7
Ethernet Communication Settings
Parameter
Default Settings
Settings