8 Communication
8.4 IEC 61850
169
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
8.4.2
PICS
(PICS = Protocol Implementation Conformance Statement)
ACSI Basic Conformance Statement
Y = supported; N or empty: not supported
Table 8-15
Basic Conformance Statement
Client/
Subscriber
Server/
Publisher
Client-Server roles
B11
Server
side (of TWO-PARTY-APPLICATION-ASSOCIATION)
-
Y
B12
Client
side of (TWO-PARTY-APPLICATION-ASSOCIATION)
N
-
SCSMs supported
B21
SCSM
: IEC 6185-8-1 used
N
Y
B22
SCSM
: IEC 6185-9-1 used
N
N
B23
SCSM
: IEC 6185-9-2 used
N
N
B24
SCSM
: other
N/A
N/A
Generic substation event model (GSE)
B31
Publisher
side
-
N
B32
Subscriber
side
N
_
Transmission of sampled value model (SVC)
B41
Publisher
side
-
N
B42
Subscriber
side
N
_