6 Operation
6.3 Configuration of the Device
74
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
Behavior when Activating the Parameter Set after the Parameter Set was Changed
Persistent:
The binary output is set to the new status (ON or OFF) as defined by the current indication.
Pulse:
If the binary output is ON in
pulse
mode while activating the parameter set, the binary output is immediately
switched to the OFF status after the parameter set has been successfully activated. This happens even if the
parameterized
Output time for pulse operating mode
has not yet elapsed.
6.3.3.3
LEDs
To change the outputs of the LEDs H1, H2 and ERROR, proceed as follows:
✧
In the navigation window, select the
Operational
menu, then the
Process connections
submenu and
click
LEDs
.
The
LEDs
input/output window opens.
Figure 6-28
Configure Tab, LEDs Input/Output Window
Table 6-4
LED Settings
LED
Default Setting
Settings
RUN
Device ready
Not settable
ERROR
-none-
Acc. to list box
H1
-none-
Acc. to list box
H2
-none-
Acc. to list box