6 Operation
6.3 Configuration of the Device
81
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
6.3.3.6
Ethernet Communication
Table 6-7
Ethernet Communication Settings
Parameter
Default Settings
Settings
IP Address
1)
192.168.0.55
Any, 0.0.0.0 at DHCP
Subnet mask
1)
255.255.255.0
Any
Default gateway
1)
192.168.0.1
Any
Ethernet switch on
no
no
yes
Bus protocol/Operating mode
Modbus TCP
-None-
Modbus TCP
Modbus UDP
I/O Mirror client
I/O Mirror server
IEC 61850
Modbus TCP
Use a user-port number
2)
no
no
yes
User-port number
2)
10000
10000 to 65535
Access rights for user port
Full
Full
Read only
Access rights for user port 502
Full
Full
Read only
Keep Alive time
10 s
0 s = switch off
1 s to 65 535 s
Communication supervision time
600 * 100 ms
0 ms = none
100 ms to 6 553 400 ms
Modbus UDP
Port number
51000
10000 to 65535
Access rights
Full
Full,
Read only
Communication supervision time
8 * 10 ms
0 ms = invalid
10 ms to 60 000 ms
I/O Mirror client
(can be parameterized, if no I/O mirror mode is selected under Communication Serial)
Server IP Address
192.168.0.56
Any
Server port
51000
10000 to 65535
Response timeout
3 * 10 ms
0 ms = invalid
10 ms to 60 000 ms
I/O Mirror server
(can be parameterized, if no I/O mirror mode is selected under Communication Serial)
Port number
51000
10000 to 65535
Communication supervision time
8 *10 ms
0 ms = invalid
10 ms to 60 000 ms