207
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
12
Operational Indications
Indication
(Relevant for Operating Mode)
Description
Notes
Device OK
Device startup successful and
ready for operation.
Indication on: Device startup successful and
ready for operation.
Start Up
Device has been started up or
restarted.
Indication on: Device has been started up or
restarted.
Battery Failure
Battery voltage < 2.7 V or no
battery inserted
Indication on: Battery failure
Clear operational log
The operational indications were
deleted.
Indication on: Operational indications deleted
Time Synchronization Error
Error during the time
synchronization from the NTP
server or fieldbus
Indication off: At least one time message was
received during the set timer ("
Error
indication after
"). The time stamp is set
when the first valid time information or time
synchronization is received.
Indication on: No time message was
received during the set timer ("
Error
indication after
").
The time stamp is set after the "
Error
indication after
" timer has expired and no
synchronization message was received.
Parameter range: see chapter 6.3.3.5
Error sources with RTC:
- no valid time after device startup
Error sources with NTP or fieldbus:
- „
Error indication after
" timer expires and
no synchronization message was received
Error during internal time
synchronization
Indication on: RTC time invalid
Indication off: After setting the clock via
HTML (see chapter 6.3.3.5)
During battery failure at device startup
Time Set
The time was set.
Indication on: Time set
Only when setting the clock via HTML