8 Communication
8.2 Modbus
150
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
8.2.8.7
Register 0131: Status of Relay Outputs
This register is write protected. A write attempt will be rejected with exception code 03
(ILLEGAL_DATA_VALUE).
Data type: Indication
Register
Type of information
Remark
0131/2
0
Relay output 1, terminal block N
Relay output 1
at the terminal block N,
terminals N1/2
0131/2
2
Relay output 2, terminal block N
Relay output 2
at the terminal block N,
terminals N3/4
0131/2
4
Relay output 3, terminal block N
Relay output 3
at the terminal block N,
terminals N5/6/7
0131/2
6
Relay output 1, terminal block P
Relay output 1
at the terminal block P,
terminals P1/2
0131/2
8
Relay output 2, terminal block P
Relay output 2
at the terminal block P,
terminals P3/4
0131/2
10
Relay output 3, terminal block P
Relay output 3
at the terminal block P,
terminals P5/6/7
0131/2
12
Reserved
= 0
0131/2
14
Reserved
= 0
MAN_SICAM_IO-Unit_7XV5673_US.book Page 150 Thursday, May 10, 2012 10:59 AM