6 Operation
6.3 Configuration of the Device
95
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
✧
Click
Generate Mapping
in the menu bar and select a folder for storing the file. In this folder, the file
7XV5673.MAP is generated.
Manual Configuration Without DIGSI 4
The manual Subscriber configuration is done according to the description of the ExtRef element in the SCD file.
The description of the ExtRef element is located below the IED node of the receiving device in the SCD file
(LN
→
Inputs
→
Extref). The following example (Figure 6-43) shows a section of an SCD file with an ExtRef-
element.
Figure 6-43
Logical Node “
ProxyGGIO1
“ of the
GGIO_BINSPC
Type (From the IED Node of the Receiving
Device)
✧
Receiver's address (points to the IED node of the
receiving
device of the SCD file):
−
intAddr
: Attribute containing the address to which the received indication is to be written. According
to IEC 61850, this section is manufacturer-dependent and must have the following content for the
SICAM I/O Unit (see Bild 6-44):
Figure 6-44
“
intAddr
“ Attribute
NOTE
The MAP file (7XV5673.MAP) can be uploaded to the device (see section Ethernet Communication Using the
IEC 61850 Bus Protocol).
NOTE
If there are several I/O units in the station, this process must be performed for each device.
NOTE
The ExtRef element describes where the GOOSE message object comes from and where the GOOSE mes-
sage object is going.