6 Operation
6.3 Configuration of the Device
69
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
6.3.3
Setting the Operational Parameters
In the
Configure
tab you can view and edit the set operational parameters. You can select the parameters in
the
Operational
menu in the navigation window. For the setting the submenus
Process connections
and
Ad-
ministrative
are available. The submenus contain the following elements
:
•
Process connections
−
Binary inputs
−
Binary outputs
−
LEDs
•
Administrative
−
Indication properties
−
Time synchronization
−
Communication Ethernet
−
Communication Serial
−
Device and Language
6.3.3.1
Binary Inputs
NOTE
Observe the procedure for the device configuration described in chapter 6.3.1 when you set the operational
parameters.
Table 6-2
Settings for Binary Inputs
Parameter
Default Settings
Setting Range
Threshold voltage
(can be set for all binary inputs individually)
19 V
19 V
88 V
176 V
Software filter time
(can be set individually for each terminal
block in 2-ms steps)
1 ms (* 2 ms)
2 ms to 120 000 ms
Binary input indication
(can be set for all binary inputs individually)
For example for terminal P8/9:
Binary input 1 - terminal block P
Arbitrary text; name of
the indication