6 Operation
6.3 Configuration of the Device
79
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
✧
In the list boxes under
End of DST
specify the month, week, day and time for switching back to standard
time
✧
Click the
Send
button.
After clicking the
Send
button, the parameters are transmitted to the device but not enabled yet (passive
parameter set).
✧
If you do not want to change any other settings, continue with the
Activation
of the device configuration
according to chapter 6.3.1.3. If you want to change other settings, enter the changes and then enable the
device configuration.
Time Synchronization via Ethernet NTP
✧
Select
Ethernet NTP
as the source from the
Source time synchronization
list box:
✧
Enter the IP address in the
Primary NTP server IP address
field.
✧
Enter the IP address of the redundant NTP server in the
Secondary NTP server IP address
field.
✧
In the
Error indication after
field enter the time in
min
after which the operational indication "Clock error"
is output.
✧
Select the time difference to UTC in the
Time zone offset to UTC
list box.
✧
The option buttons at
Daylight Saving Time switchover
allow you to enable (
yes
) or disable (
no
) the
automatic Daylight Saving Time adjustment.
If you have selected the
no
option button, the time synchronization is complete. Click the
Send
button in
this case. If you have selected the yes option button, continue the parameterization as follows:
✧
Select the time difference to UTC in the
DST offset to UTC
list box.
✧
In the list boxes under
Start of DST
specify the month, week, day and time for starting Daylight Saving
Time.
✧
In the list boxes under
End of DST
specify the month, week, day and time for switching back to standard
time.
✧
Click the
Send
button.
After clicking the
Send
button, the parameters are transmitted to the device but not enabled yet (passive
parameter set).
✧
If you do not want to change any other settings, continue with the
Activation
of the device configuration
according to chapter 6.3.1.3. If you want to change other settings, enter the changes and then enable the
device configuration.
Time Synchronization via Fieldbus (Modbus)
✧
Select
Fieldbus
as the source from the
Source time synchronization
list box:
✧
In the
Error indication after
field enter the time in
min
after which the operational indication "Clock error"
is output.
✧
Select the time difference to UTC in the
Time zone offset to UTC
list box.
✧
The option buttons at
Daylight Saving Time switchover
allow you to enable (
yes
) or disable (
no
) the
automatic Daylight Saving Time adjustment.
NOTE
If the IEC 61850 protocol is used, NTP synchronization must be selected.
MAN_SICAM_IO-Unit_7XV5673_US.book Page 79 Thursday, May 10, 2012 10:59 AM