11 Technical Data
11.1 General Device Data
198
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
Transmission Times Between 2 Devices from Binary Input to Relay Output
Transmission times between 2 devices from applying the signal voltage on the binary input of the 1
st
device to
triggering the parameterized relay contact (binary output) on the 2
nd
device
11.1.3
Communication Interfaces
Ethernet
Ethernet transmission
Conditions:
Software filter time of the binary inputs:
≥
2 ms
Local communication net (only I/O mirror server/client)
Minimum Transmission Time
Medium Transmission Time
Maximum Transmission Time
9.7 ms
10.97 ms
12.00 ms
Optical transmission
Condition:
Software filter time of the binary inputs:
≥
2 ms
Baud Rate
Minimum Transmission Time
Medium Transmission Time
Maximum Transmission Time
187 500 bit/s
10.1 ms
10.68 ms
11.6 ms
115 200 bit/s
9.9 ms
10.57 ms
11.4 ms
57 600 bit/s
12.4 ms
13.81 ms
15.7 ms
38 400 bit/s
11.6 ms
15.41 ms
18.9 ms
19 200 bit/s
15.4 ms
20.03 ms
24.3 ms
9600 bit/s
21.1 ms
32.56 ms
42.3 ms
4800 bit/s
34.9 ms
52.81 ms
74.6 ms
2400 bit/s
55.4 ms
87.85 ms
139.2 ms
1200 bit/s
112.6 ms
179.41 ms
268.9 ms
Ethernet, electrical
Operation
With device internal software
Connection
Device top side
RJ45 connector socket
100BaseT acc. to IEEE802.3
LED yellow: 10/100 Mbit/s (off/on)
LED green: connection/no connection
(on/off)
Protocols
Modbus TCP
Modbus UDP
IEC 61850
Voltage strength
DC 700 V
Transmission rate
10/100 Mbit/s
Cable for 100Base-T
100
Ω
to 150
Ω
STP, CAT5
Max. cable lenght
100Base-T
100 m, if well installed
MAN_SICAM_IO-Unit_7XV5673_US.book Page 198 Thursday, May 10, 2012 10:59 AM