6 Operation
6.3 Configuration of the Device
72
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
✧
Select the
Source
of the message from the
Indication
list box. You can select the following messages:
−
Ready and status indications, for example Device OK, Modbus TCP OK
−
Indications about present device activities, for example Settings load
−
Error indications, for example Battery Failure, Ethernet Link Error
−
Administrative indications, for example Daylight Saving Time
−
Communication indications, for example Indication 1 from Remote
−
Indications to the binary inputs, for example Binary input 1 - Terminal block 1
Select
-none-
to disable the binary output.
✧
In the
Source inverted
section select whether you want to invert the indication for the output (
yes
) or not
(
no
).
✧
Select the output mode at the binary outputs in the
Operating mode
list box. The following output types
are available:
−
Persistent
: The binary output has the status ON or OFF. If the indication becomes invalid, the binary
output continues to maintain its current status.
Figure 6-24
Persistent
−
Fail-safe persistent output
: If the message becomes invalid and
Source inverted = no
has been
parameterized, the binary output switches to OFF mode. If the message becomes invalid and
Source
inverted = yes
has been parameterized, the binary output switches to ON mode.
Figure 6-25
Persistent with Fail Save
invalid
Binary output
inverted
Indication
Indication
Output
Binary output
not inverted
invalid
ON
Output
ON
OFF
OFF
ON
OFF
invalid
Binary output
inverted
Indication
Indication
Output
Binary output
not inverted
invalid
ON
Output
ON
OFF
OFF
ON
OFF