6 Operation
6.3 Configuration of the Device
77
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
✧
In the list box, select the message which is to appear in the operational log.
✧
Click the
Send
button.
After clicking the
Send
button, the parameters are transmitted to the device but not enabled yet (passive
parameter set).
✧
If you do not want to change any other settings, continue with the
Activation
of the device configuration
according to chapter 6.3.1.3. If you want to change other settings, enter the changes and then enable the
device configuration.
6.3.3.5
Time Synchronization
Table 6-6
Time Synchronization Settings
Parameter
Default Setting
Settings
Source time synchronization
Internal
Internal
Ethernet NTP
Fieldbus
Time zone offset to UTC
+00:00
-12 to +13 (hours)
(in increments of 0.5 h)
Daylight saving time switchover
yes
no
yes
DST offset to UTC
+01:00
0 to + 2 (hours)
(in increments of 0.5 h)
Start of DST
March
Last week
Sunday
02:00 AM
Acc. to list box
(see chapter 13.2.2)
End of DST
October
Last week
Sunday
03:00 AM
Acc. to list box
(see chapter 13.2.2)
Additional parameters if the source is Ethernet NTP
Primary NTP server IP address
192.168.0.254
Any
Secondary NTP server IP address
192.168.0.253
Any
Error indication after
10 min
2 min to 120 min
Additional parameter if the source is Fieldbus (Modbus RTU)
Error indication after
10 min
2 min to 120 min