6 Operation
6.3 Configuration of the Device
92
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
Case 3: File upload successful: Active Edition does not match file Edition
The Edition 1 configuration is uploaded. Edition 2 is selected in the
IEC 61850 Edition
list box; the
configuration is stored but does not become effective. The configuration will only become effective
after having selected Edition 1 from the
IEC 61850 Edition
list box and restarted the device.
Figure 6-41
File Upload Successful: Active Edition Does Not Match File Edition
✧
In the
Use settings in the table below
option field (see Figure 6-36), select the option:
−
yes
if you want to manually set the GOOSE publisher parameters. The settings from the pre-installed
or uploaded configuration are then overwritten. In this way, the device can be configured as publisher
with simple means without using the SICAM I/O Mapping Tool and without DIGSI.
−
no
if:
1. You want to take over the parameters generated in DIGSI and edited with the SICAM I/O Mapping
Tool (see section
2. You want to take over the configuration already pre-installed in the device upon delivery.
✧
Change the serial number of the SICAM I/O Unit in the
IED name number
(factory setting 1) if several
SICAM I/O Units are used in the substation. The number must be identical with the number parameterized
for this SICAM I/O Unit in the configurator of the substation.
The following parameters describe the configuration of the GOOSE publishers (inputs/outputs):
✧
Enter the hexadecimal multicast address [xx-xx-xx-xx-xx-xx] in the
Multicast MAC address
field.
✧
Enter the hexadecimal App ID [xxxx] in the
App ID
field.
✧
Enter the hexadecimal VLAN ID [xxx] in the
VLAN ID
field.
NOTE
By stating the
IED name number
, the SICAM I/O Unit is uniquely identified in the network.