Chapter 4 - 7SR105 Rho · Data Communications Definitions
© 2018 Siemens Protection Devices
Chapter 4 - Page 55 of 70
Counters
Static (Steady-State) Object Number: 20
Change Event Object Number: 22
Static Variation reported when variation 0 requested: 1 (32-Bit Counter with Flag)
or 2 (16-Bit Counter with Flag)
or 5 (32-Bit Counter w/o Flag)
or 6 (16-Bit Counter w/o Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Counter Event with Flag)
or 2 (16-Bit Counter Event with Flag)
or 5 (32-Bit Counter Event with Flag and Time)
or 6 (16-Bit Counter Event with Flag and Time)
Frozen Counters
Static (Steady-State) Object Number: 21
Change Event Object Number: 23
Static Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter with Flag)
or 2 (16-Bit Frozen Counter with Flag)
or 5 (32-Bit Frozen Counter with Flag and Time)
or 6 (16-Bit Frozen Counter with Flag and Time)
or 9 (32-Bit Frozen Counter w/o Flag)
or 10 (16-Bit Frozen Counter w/o Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter Event with Flag)
or 2 (16-Bit Frozen Counter Event with Flag)
or 5 (32-Bit Frozen Counter Event with Flag and Time)
or 6 (16-Bit Frozen Counter Event with Flag and Time)
Counter
Frozen Counter
Point
Index
Description
Default
Change
Event
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Static
Object 20
Default
Variation
Event
Object 22
Deadband
Is Resettable
IsFreezable
Default
Change
Event
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Static
Object 21
Default
Variation
Event
Object 23
0 Waveform Records
0,3
5
1
1
✔
0,2
9
1
1 Fault Records
0,3
5
1
1
✔
0,2
9
1
2 Event Records
0,3
5
1
1
✔
0,2
9
1
3 Data Log Records
0,3
5
1
1
✔
0,2
9
1
4 Number User Files
0,3
5
1
1
✔
0,2
9
1
5 StartCount
0,3
5
1
1
✔ ✔
0,2
9
1
6 Start Count Target
0,3
5
1
1
✔
0,2
9
1
7 Active Setting Group
0,3
5
1
1
✔
0,2
9
1
11 CB Total Trip Count
0,3
5
1
1
✔ ✔
0,2
9
1
16 CB Delta Trip Count
0,3
5
1
1
✔ ✔
0,2
9
1
21 E1 Counter
0,3
5
1
1
✔
0,2
9
1
22 E2 Counter
0,3
5
1
1
✔
0,2
9
1
23 E3 Counter
0,3
5
1
1
✔
0,2
9
1
24 E4 Counter
0,3
5
1
1
✔
0,2
9
1
5.3.5 Analog Inputs
The following table lists Analog Inputs (Object 30). It is important to note that 16-bit and 32-bit variations of Analog
Inputs, Analog Output Control Blocks, and Analog Output Statuses are transmitted through DNP as signed numbers.
The “Default Deadband,” and the “Default Change Event Assigned Class” columns are used to represent the absolute
amount by which the point must change before an Analog change event will be generated, and once generated in
which class poll (1, 2, 3, or none) will the change event be reported.
The default analog input event buffer size is set 30. The analog input event mode is set to Most Recent, only most
recent event for each point is stored.
Summary of Contents for 7SR105 Rho
Page 1: ...Answers for energy 7SR105 Rho User Manual Motor Protection Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices 2 ...
Page 95: ...7SR105 Rho Technical Manual Chapter 4 Page 2 of 70 2018 Siemens Protection Devices ...
Page 99: ...7SR105 Rho Technical Manual Chapter 4 Page 6 of 70 2018 Siemens Protection Devices ...
Page 127: ...7SR105 Rho Technical Manual Chapter 4 Page 34 of 70 2018 Siemens Protection Devices ...
Page 153: ...7SR105 Rho Technical Manual Chapter 4 Page 60 of 70 2018 Siemens Protection Devices ...
Page 155: ...7SR105 Rho Technical Manual Chapter 4 Page 62 of 70 2018 Siemens Protection Devices ...
Page 157: ...7SR105 Rho Technical Manual Chapter 4 Page 64 of 70 2018 Siemens Protection Devices ...