©2018 Siemens Protection Devices Limited Chapter 2 Page 14 of 16
2.1.3 Configuring Relay Serial Data Communication
Using the keys on the relay fascia scroll down the settings menus into the ‘communications’ menu and if
necessary change the settings for the communication port you are using on the relay. Reydisp software uses
IEC60870-5-103 protocol to communicate.
When connecting the relay to a pc using the front USB port, the Reydisp setting software will automatically detect
the relay without making any setting changes in the relay first as long as the USB is selected to IEC60870-5-103.
COM1-RS485 Port and COM2-USB Port
Description
Range
Default
Notes
COM1-RS485 Protocol
Selects protocol to use for COM1-RS485
OFF, IEC60870-5-103,
MODBUS-RTU, DNP3
IEC60870-5-103
COM1-RS485 Station Address
IEC 60870-5-103 Station Address
0, 1 ... 65533, 65534
0
Address given to relay
to identify that relay
from others which may
be using the same path
for communication as
other relays for
example in a fibre optic
hub
COM1-RS485 Baud Rate
Sets the communications baud rate for COM1-
RS485
75, 110, 150, 300, 600, 1200,
2400, 4800, 9600, 19200,
38400
19200
19200
COM1-RS485 Parity
Selects whether parity information is used
NONE, ODD, EVEN
EVEN
EVEN
COM1-RS485 Mode
Selects whether the port is Local or Remote.
Local, Remote, Local Or
Remote
Remote
Remote
COM2-USB Protocol
Selects protocol to use for COM2-USB
OFF, DNP3, ASCII, MODBUS-
RTU, IEC60870-5-103
IEC60870-5-103
COM2-USB Station Address
IEC 60870-5-103 Station Address
0, 1 ... 65533, 65534
0
Address given to relay
to identify it for
connection to the USB
front port
COM2-USB Mode
Selects whether the port is Local or Remote.
Local, Remote, Local Or
Remote
Local
Local
DNP3 Unsolicited Events
Allows unsolicited event support in the relay.
When Enabled, unsolicited event transmission
can be controlled by the Master. When
Disabled, Master requests are ignored.
Disabled, Enabled
Disabled
Disabled
DNP3 Destination Address
The address of the master to which unsolicited
events will be sent.
0, 1 ... 65533, 65534
0
This setting is only
visible when DNP3
Unsolicited Events is
Enabled
DNP3 Application Timeout
5, 6 ... 299, 300
10s
10s
Summary of Contents for 7SR105 Rho
Page 1: ...Answers for energy 7SR105 Rho User Manual Motor Protection Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices 2 ...
Page 95: ...7SR105 Rho Technical Manual Chapter 4 Page 2 of 70 2018 Siemens Protection Devices ...
Page 99: ...7SR105 Rho Technical Manual Chapter 4 Page 6 of 70 2018 Siemens Protection Devices ...
Page 127: ...7SR105 Rho Technical Manual Chapter 4 Page 34 of 70 2018 Siemens Protection Devices ...
Page 153: ...7SR105 Rho Technical Manual Chapter 4 Page 60 of 70 2018 Siemens Protection Devices ...
Page 155: ...7SR105 Rho Technical Manual Chapter 4 Page 62 of 70 2018 Siemens Protection Devices ...
Page 157: ...7SR105 Rho Technical Manual Chapter 4 Page 64 of 70 2018 Siemens Protection Devices ...