7SR105 Rho and 7SR17 Rho Applications Guide
©2018 Siemens Protection Devices
Chapter 7 Page 24 of 31
4.6 Trip/Close Circuit Supervision (74T/CCS)
The relay provides three trips and three close circuit supervision elements, all elements are identical in operation
and independent from each other allowing 3 trip and 3 close circuits to be monitored.
One or more binary inputs can be mapped to
74TCS-n.
The inputs are connected into the trip circuit such that at
least one input is energised when the trip circuit wiring is intact. If all the mapped inputs become de-energised,
due to a break in the trip circuit wiring or loss of supply an output is given.
The
74TCS-n Delay
setting prevents the failure being incorrectly indicated during circuit breaker operation. This
delay should be greater than the operating time of the circuit breaker.
The use of one or two binary inputs mapped to the same Trip Circuit Supervision element (e.g. 74TCS-n) allows
the user to realise several alternative monitoring schemes.
TCS-n
Enabled
Disabled
&
74TCS-n
74TCS-n
74TCS-n Delay
≥1
74TCS-n
NOTE: Diagram shows two binary inputs mapped
to the same Trip Circuit Supervision element
Figure 4-1 Logic Diagram: Trip Circuit Supervision Feature (74TCS)
CCS-n
Enabled
Disabled
&
74CCS-n
74CCS-n Delay
≥1
74CCS-n
NOTE: Diagram shows two binary inputs mapped
to the same Close Circuit Supervision element
74CCS-n
Figure 4-2 Logic Diagram: Close Circuit Supervision Feature (74CCS)
4.6.1 Trip Circuit Supervision Connections
The following circuits are derived from UK ENA S15 standard schemes H5, H6 and H7.
For compliance with this standard:
Where more than one device is used to trip the CB then connections should be looped between the
tripping contacts. To ensure that all wiring is monitored the binary input must be at the end of the looped
wiring.
Resistors must be continuously rated and where possible should be of wire-wound construction.
Summary of Contents for 7SR105 Rho
Page 1: ...Answers for energy 7SR105 Rho User Manual Motor Protection Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices 2 ...
Page 95: ...7SR105 Rho Technical Manual Chapter 4 Page 2 of 70 2018 Siemens Protection Devices ...
Page 99: ...7SR105 Rho Technical Manual Chapter 4 Page 6 of 70 2018 Siemens Protection Devices ...
Page 127: ...7SR105 Rho Technical Manual Chapter 4 Page 34 of 70 2018 Siemens Protection Devices ...
Page 153: ...7SR105 Rho Technical Manual Chapter 4 Page 60 of 70 2018 Siemens Protection Devices ...
Page 155: ...7SR105 Rho Technical Manual Chapter 4 Page 62 of 70 2018 Siemens Protection Devices ...
Page 157: ...7SR105 Rho Technical Manual Chapter 4 Page 64 of 70 2018 Siemens Protection Devices ...