7SR105 Rho Technical Manual
Chapter 4 - Page 40 of 70
© 2018 Siemens Protection Devices
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Description
Function Codes
(dec)
Qualifier Codes
(hex)
Function
Codes
(dec)
Qualifier Codes
(hex)
20
6
16-Bit Binary Counter
(without Flag)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
20
7
32-Bit Delta Counter
(without Flag)
20
8
16-Bit Delta Counter
(without Flag)
21
0
Frozen Counter
- Any Variation
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
21
1
32-Bit Frozen Counter
(with Flag)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
21
2
16-Bit Frozen Counter
(with Flag)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
21
3
32-Bit Frozen Delta
Counter (with Flag)
21
4
16-Bit Frozen Delta
Counter (with Flag)
21
5
32-Bit Frozen Counter
(without Time Of Freeze)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
21
6
16-Bit Frozen Counter
(without Time Of Freeze)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
21
7
32-Bit Frozen Delta Counter
(with Time Of Freeze)
21
8
16-Bit Frozen Delta Counter
(with Time Of Freeze)
21
9 (default -
see note 1)
32-Bit Frozen Counter
(without Flag)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
21
10
16-Bit Frozen Counter
(without Flag)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
21
11
32-Bit Frozen Delta Counter
(without Flag)
21
12
16-Bit Frozen Delta Counter
(without Flag)
22
0
Counter Change Event
- Any Variation
1 (read)
06 (no range, or all)
07, 08 (limited qty)
22
1 (default -
see note 1)
32-Bit Counter Change
Event (without Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
22
2
16-Bit Counter Change
Event (without Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
22
3
32-Bit Delta Counter
Change Event
(without Time)
22
4
16-Bit Delta Counter
Change Event
(without Time)
22
5
32-Bit Counter Change
Event (with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
22
6
16-Bit Counter Change
Event (with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
17, 28 (index)
Summary of Contents for 7SR105 Rho
Page 1: ...Answers for energy 7SR105 Rho User Manual Motor Protection Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices 2 ...
Page 95: ...7SR105 Rho Technical Manual Chapter 4 Page 2 of 70 2018 Siemens Protection Devices ...
Page 99: ...7SR105 Rho Technical Manual Chapter 4 Page 6 of 70 2018 Siemens Protection Devices ...
Page 127: ...7SR105 Rho Technical Manual Chapter 4 Page 34 of 70 2018 Siemens Protection Devices ...
Page 153: ...7SR105 Rho Technical Manual Chapter 4 Page 60 of 70 2018 Siemens Protection Devices ...
Page 155: ...7SR105 Rho Technical Manual Chapter 4 Page 62 of 70 2018 Siemens Protection Devices ...
Page 157: ...7SR105 Rho Technical Manual Chapter 4 Page 64 of 70 2018 Siemens Protection Devices ...