7SR105 Rho Performance Specification
© 2018 Siemens Protection Devices
Chapter 3 Page 13 of 17
1.4 Performance Specification
This section describes about the settings available for different protection functions and its tolerance limits.
Table 1-19
14 Stall Protection
Number of Elements
4
Setting Range I
s
0.05 to 10xI
n
Time Delay
0.00 to 14400 s
Operate Level
100 % Is ± 5 % or ±1 %xI
n
Operate time
2 x I
s
5 x I
s
35 ms ± 10 ms,
25 ms ± 10 ms
Operate time following delay
t
basic
+t
d
, ±1 % or ± 10 ms
Controlled by
Stopped, No acceleration, Running, None
Disengaging time
< 50 ms
Table 1-20
37 Undercurrent
Number of Elements
2
U/C Guard
0.05 to 5.0xI
n
Setting Range I
s
0.05 to 5.0xI
n
Operate Level
100 % I
s
± 5 % or ± 1 %xI
n
Delay Setting td
0 to 14400 s
Basic Operate Time: -
0.5 x Is
35 ms ± 20 ms
Operate time following delay
t
basic
+ t
d
, ± 1 % or ± 10 ms
Overshoot Time
< 40 ms
Inhibited by
Binary or Virtual Input
Disengaging time
< 60 ms
Summary of Contents for 7SR105 Rho
Page 1: ...Answers for energy 7SR105 Rho User Manual Motor Protection Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices 2 ...
Page 95: ...7SR105 Rho Technical Manual Chapter 4 Page 2 of 70 2018 Siemens Protection Devices ...
Page 99: ...7SR105 Rho Technical Manual Chapter 4 Page 6 of 70 2018 Siemens Protection Devices ...
Page 127: ...7SR105 Rho Technical Manual Chapter 4 Page 34 of 70 2018 Siemens Protection Devices ...
Page 153: ...7SR105 Rho Technical Manual Chapter 4 Page 60 of 70 2018 Siemens Protection Devices ...
Page 155: ...7SR105 Rho Technical Manual Chapter 4 Page 62 of 70 2018 Siemens Protection Devices ...
Page 157: ...7SR105 Rho Technical Manual Chapter 4 Page 64 of 70 2018 Siemens Protection Devices ...