Chapter 4 - 7SR105 Rho · Data Communications Definitions
© 2018 Siemens Protection Devices
Chapter 4 - Page 43 of 70
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Description
Function Codes
(dec)
Qualifier Codes
(hex)
Function
Codes
(dec)
Qualifier Codes
(hex)
17, 27, 28 (index)
2 (write)
00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
50
0
Time and Date
1 (read)
07, 08 (limited qty)
129
(response)
07 (limited qty = 1)
50
1 (default -
see note 1)
Time and Date
2 (write)
00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
50
3
Time and Date Last
Recorded Time
2 (write)
07 (limited qty)
51
1
Time and Date CTO
129
(response)
130
(unsol. resp)
(limited qty = 1)
51
2
Unsynchronized
Time and Date CTO
129
(response)
130
(unsol. resp)
(limited qty = 1)
52
1
Time Delay Coarse
129
(response)
(limited qty = 1)
52
2
Time Delay Fine
129
(response)
(limited qty = 1)
60
0
Not Defined
60
1
Class 0 Data
1 (read)
06 (no range, or all)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
60
2
Class 1 Data
20 (enbl. unsol.)
21 (dab. unsol.)
22 (assign class)
06 (no range, or all)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
60
3
Class 2 Data
20 (enbl. unsol.)
21 (dab. unsol.)
22 (assign class)
06 (no range, or all)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
60
4
Class 3 Data
20 (enbl. unsol.)
21 (dab. unsol.)
22 (assign class)
06 (no range, or all)
1 (read)
00, 01 (start-stop)
129
(response)
00, 01 (start-stop)
80
1
Internal Indications
2 (write)(see note 3)
00 (start-
stop) index=7
No Object
(function code only)
13 (cold restart)
No Object
(function code only)
14 (warm restart)
No Object
(function code only)
23 (delay meas.)
No Object
(function code only)
24 (record
current time)
Note 1: A Default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or
3 scans. Default variations are configurable; however, default settings for the configuration parameters are indicated
in the table above.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with
qualifiers 17 or 28, respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be
responded with qualifiers 00 or 01. (For change-event objects, qualifiers 17 or 28 are always responded.)
Note 3: Writes of Internal Indications are only supported for index 7 (Restart IIN1-7).
Summary of Contents for 7SR105 Rho
Page 1: ...Answers for energy 7SR105 Rho User Manual Motor Protection Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices 2 ...
Page 95: ...7SR105 Rho Technical Manual Chapter 4 Page 2 of 70 2018 Siemens Protection Devices ...
Page 99: ...7SR105 Rho Technical Manual Chapter 4 Page 6 of 70 2018 Siemens Protection Devices ...
Page 127: ...7SR105 Rho Technical Manual Chapter 4 Page 34 of 70 2018 Siemens Protection Devices ...
Page 153: ...7SR105 Rho Technical Manual Chapter 4 Page 60 of 70 2018 Siemens Protection Devices ...
Page 155: ...7SR105 Rho Technical Manual Chapter 4 Page 62 of 70 2018 Siemens Protection Devices ...
Page 157: ...7SR105 Rho Technical Manual Chapter 4 Page 64 of 70 2018 Siemens Protection Devices ...