Chapter 4 - 7SR105 Rho · Data Communications Definitions
© 2018 Siemens Protection Devices
Chapter 4 - Page 25 of 70
Byte
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Content
2
0
FUN
INF
DPI RT L
RT
H
F# L F# H
0
0
0
ms L
ms
H
Mi
Ho
Event Type 2 Format.
Byte
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Content
4
0
FUN
INF
Meas
0
0
0
0
ms L
ms
H
Mi
Ho
Event Type 4 Format.
4.2.6 EVENTCOUNT
The EVENTCOUNT register contains the current number of events in the relay's event buffer.
On reception this register should be interpreted as a 16 bit integer.
4.2.7 TIME_METER
The TIME_METER register contains the device's time. The time must be read or written in one step;
therefore the quantity should be 4 registers. Failing to do this will result in an exception code 2. The
time format is 8 bytes as follows.
The following table describes the fields in the time.
Key
Description
ms L
Time Stamp Milliseconds low byte.
ms H
Time Stamp Milliseconds high byte.
Mi
Time Stamp Minutes (MSB = invalid, time not set > 23 hours).
Ho
Time Stamp Hours (MSB = Summer time flag).
Da
Time Stamp Days.
Mo
Time Stamp Months.
Ye L
Time Stamp Years low byte.
Ye H
Time Stamp Years high byte (Not Used).
The following table shows the fields in the time as they are returned.
Byte
0
1
2
3
4
5
6
7
Content
ms L ms H
Mi
Ho
Da
Mo
Ye L Ye H
Time Format.
4.2.8 STR32 & STR64
4.2.9 BITSTRING
A Bit-String (or Bit-Array) is a method of compactly storing a number of bits of data. In this instance we store
up to 16 bit values, for example the states of binary inputs, in a single 16 bit register. The first bit value is
stored in the Least Significant Bit (LSB) of the register. The 16
th
value would be in the Most Significant Bit
(MSB). Bit values can only be zero or one. Any unused bits will be set to zero.
BITSTRING & MODBUS
Summary of Contents for 7SR105 Rho
Page 1: ...Answers for energy 7SR105 Rho User Manual Motor Protection Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices 2 ...
Page 95: ...7SR105 Rho Technical Manual Chapter 4 Page 2 of 70 2018 Siemens Protection Devices ...
Page 99: ...7SR105 Rho Technical Manual Chapter 4 Page 6 of 70 2018 Siemens Protection Devices ...
Page 127: ...7SR105 Rho Technical Manual Chapter 4 Page 34 of 70 2018 Siemens Protection Devices ...
Page 153: ...7SR105 Rho Technical Manual Chapter 4 Page 60 of 70 2018 Siemens Protection Devices ...
Page 155: ...7SR105 Rho Technical Manual Chapter 4 Page 62 of 70 2018 Siemens Protection Devices ...
Page 157: ...7SR105 Rho Technical Manual Chapter 4 Page 64 of 70 2018 Siemens Protection Devices ...