Chapter 4 - 7SR105 Rho · Data Communications Definitions
© 2018 Siemens Protection Devices
Chapter 4 - Page 11 of 70
3. IEC 60870-5-103 Definitions
3.1 Introduction
This section describes the IEC 60870-5-103 protocol implementation in the relays. This protocol is used for the
communication with Reydisp software and can also be used for communication with a suitable control system.
The control system or local PC acts as the master in the system with the relay operating as a slave responding
to the master's commands. The implementation provides event information, time synchronising, commands and
measurands and also supports the transfer of disturbance records.
This protocol can be set to use any or all of the relays hardware interfaces (USB and RS485) where fitted and is
the standard protocol used by the USB port. The relay can communicate simultaneously on all ports regardless of
protocol used.
The Station Address of the port being used must be set to a suitable address within the range 0 - 254 to enable
communication. This can be set by the Communications Menu : COM n-xxxxx Station Address setting.
Summary of Contents for 7SR105 Rho
Page 1: ...Answers for energy 7SR105 Rho User Manual Motor Protection Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices 2 ...
Page 95: ...7SR105 Rho Technical Manual Chapter 4 Page 2 of 70 2018 Siemens Protection Devices ...
Page 99: ...7SR105 Rho Technical Manual Chapter 4 Page 6 of 70 2018 Siemens Protection Devices ...
Page 127: ...7SR105 Rho Technical Manual Chapter 4 Page 34 of 70 2018 Siemens Protection Devices ...
Page 153: ...7SR105 Rho Technical Manual Chapter 4 Page 60 of 70 2018 Siemens Protection Devices ...
Page 155: ...7SR105 Rho Technical Manual Chapter 4 Page 62 of 70 2018 Siemens Protection Devices ...
Page 157: ...7SR105 Rho Technical Manual Chapter 4 Page 64 of 70 2018 Siemens Protection Devices ...