Analog inputs are by default returned in a class zero interrogation.
Note, not all points listed here apply to all builds of devices.
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Analog Input Deadband: 34
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag)
or 2 (16-Bit Analog Input with Flag)
or 3 (32-Bit Analog Input w/o Flag)
or 4 (16-Bit Analog Input w/o Flag)
or 5 (Single Precision, floating point Analog Input with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time)
or 2 (16-Bit Analog Input w/o Time)
or 3 (32-Bit Analog Input with Time)
or 4 (16-Bit Analog Input with Time)
or 5 (Single Precision, floating point Analog Input w/o Time)
or 7 (Single Precision, floating point Analog Input with Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit)
or 2 (32-Bit)
or 3 (Single Precision, floating point)
Point
Index
Description
Default
Change Event
Assigned Class
(1, 2, 3 or none)
Default
Variation
Static
Object 30
Default
Variation
Event
Object 32
Default
Multiplier
Default
Deadband
31 Ia Primary
0,3
2
4
1.000
10.000
32 Ib Primary
0,3
2
4
1.000
10.000
33 Ic Primary
0,3
2
4
1.000
10.000
34 Ia Secondary
0,3
2
4
100.000
0.100
35 Ib Secondary
0,3
2
4
100.000
0.100
36 Ic Secondary
0,3
2
4
100.000
0.100
37 Ia Nominal
0,3
2
4
100.000
0.100
38 Ib Nominal
0,3
2
4
100.000
0.100
39 Ic Nominal
0,3
2
4
100.000
0.100
43 In Primary
0,3
2
4
1.000
10.000
44 In Secondary
0,3
2
4
100.000
0.100
45 In Nominal
0,3
2
4
100.000
0.100
46 Ig Primary
0,3
2
4
1.000
10.000
47 Ig Secondary
0,3
2
4
1000.000
0.100
48 Ig Nominal
0,3
2
4
1000.000
0.100
51 Izps Nominal
0,3
2
4
100.000
0.100
52 Ipps Nominal
0,3
2
4
100.000
0.100
53 Inps Nominal
0,3
2
4
100.000
0.100
95 Active Setting Group
0,3
2
4
1.000
1.000
108 I Phase A Max
0,3
2
4
1.000
10.000
109 I Phase B Max
0,3
2
4
1.000
10.000
110 I Phase C Max
0,3
2
4
1.000
10.000
113 Ig Max
0,3
2
4
1.000
10.000
135 CB Total Trip Count
0,3
1
3
1.000
1.000
136 CB Delta Trip Count
0,3
1
3
1.000
1.000
165 Ia Last Trip
0,3
1
3
1.000
Disabled
166 Ib Last Trip
0,3
1
3
1.000
Disabled
167 Ic Last Trip
0,3
1
3
1.000
Disabled
171 In Last Trip
0,3
1
3
1.000
Disabled
172 Ig Last Trip
0,3
1
3
1.000
Disabled
Summary of Contents for 7SR105 Rho
Page 1: ...Answers for energy 7SR105 Rho User Manual Motor Protection Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices 2 ...
Page 95: ...7SR105 Rho Technical Manual Chapter 4 Page 2 of 70 2018 Siemens Protection Devices ...
Page 99: ...7SR105 Rho Technical Manual Chapter 4 Page 6 of 70 2018 Siemens Protection Devices ...
Page 127: ...7SR105 Rho Technical Manual Chapter 4 Page 34 of 70 2018 Siemens Protection Devices ...
Page 153: ...7SR105 Rho Technical Manual Chapter 4 Page 60 of 70 2018 Siemens Protection Devices ...
Page 155: ...7SR105 Rho Technical Manual Chapter 4 Page 62 of 70 2018 Siemens Protection Devices ...
Page 157: ...7SR105 Rho Technical Manual Chapter 4 Page 64 of 70 2018 Siemens Protection Devices ...