2.2 USB Interface (COM2)
The USB communication port is connected using a standard USB cable with a type B connection to the relay and
type A to the PC.
The PC will require a suitable USB driver to be installed; this will be carried out automatically when the Reydisp
software is installed. When the Reydisp software is running with the USB cable connected to a device an additional
connection is shown. Connections to these devices are not shown when they are not connected.
The USB communication interface on the relay is labelled Com 2 and its associated settings are located in the Data
communications menu. When connecting to Reydisp using this connection the default settings can be used without
the need to first change any settings.
Access to the communication settings for the USB port is only available from the relay front fascia via the key pad
setting menu COMMUNICATIONS MENU.
Setting Name
Range/Options
Default
Setting
Notes
COM2-USB
Protocol
OFF
IEC60870-5-103
MODBUS-RTU
ASCII
DNP3
IEC60870-5-103
Reydisp
software requires
IEC60870-5-103.
COM2-USB
Station
Address
0 - 254 for IEC60870-5-103
1 - 247 for Modbus RTU
0 - 65534 for DNP3.0
0
An address within the
range of the relevant
protocol must be
given to identify the
relay. Each relay in a
network must have a
unique address.
COM2-USB
Mode
Local
Local or Remote
Remote
Local
, for
further explanation
USB Type A
Socket on PC
USB Type B
Socket on Device
Local Engineer Access
Fig. 2-1 Communication to Front USB Port
2.3 RS485 Interface (COM1)
The 2-wire RS485 communication port is located on the rear of the relay and can be connected using a suitable
RS485 120 Ohm screened twisted pair cable.
Summary of Contents for 7SR105 Rho
Page 1: ...Answers for energy 7SR105 Rho User Manual Motor Protection Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices 2 ...
Page 95: ...7SR105 Rho Technical Manual Chapter 4 Page 2 of 70 2018 Siemens Protection Devices ...
Page 99: ...7SR105 Rho Technical Manual Chapter 4 Page 6 of 70 2018 Siemens Protection Devices ...
Page 127: ...7SR105 Rho Technical Manual Chapter 4 Page 34 of 70 2018 Siemens Protection Devices ...
Page 153: ...7SR105 Rho Technical Manual Chapter 4 Page 60 of 70 2018 Siemens Protection Devices ...
Page 155: ...7SR105 Rho Technical Manual Chapter 4 Page 62 of 70 2018 Siemens Protection Devices ...
Page 157: ...7SR105 Rho Technical Manual Chapter 4 Page 64 of 70 2018 Siemens Protection Devices ...