7SR105 Rho Description of Operation
©2018 Siemens Protection Devices Chapter 1 Page 37 of 57
I
G
&
50G-n
General Pickup
Enabled
Disabled
Gn 50G- n Element
EF In
Inhibit 50G-n
50 G Measurement
>
En
Gn 50G- n Setting
Gn 50G- n Delay
Figure 3-15 Logic Diagram: Measured Instantaneous Earth-fault Element
3.5.2 Time Delayed Measured Earth Fault Protection (51G)
Two instantaneous measured earth fault elements are provided in the 7SR105 Rho Motor Protection Relay.
51G-1, 51G-2
51G-n Setting
sets the pick-up current level.
A number of shaped characteristics are provided. An inverse definite minimum time (IDMT) characteristic is
selected from IEC and ANSI curves using
51G-n Char
. A time multiplier is applied to the characteristic curves
using the
51G-n Time Mult
setting. Alternatively, a definite time lag (DTL) can be chosen using
51G-n Char
.
When DTL is selected the time multiplier is not applied and the
51G-n Delay (DTL)
setting is used instead.
The
51G-n Reset
setting can apply a
definite time delayed
reset or when the operation is configured as an IEC
or ANSI curves if the reset is selected as
IEC/ANSI (DECAYING)
reset the associated reset curve will be used.
The reset mode is significant where the characteristic has reset before issuing a trip output.
A minimum operate time for the characteristic can be set using
51G-n Min. Operate Time
setting.
A fixed additional operate time can be added to the characteristic using
51G-n Follower DTL
setting.
Operation of the time delayed measured earth fault elements can be inhibited from:
Inhibit 51G-n
A binary or virtual input.
I
G
&
Enabled
Disabled
Gn 51G- n Element
EF In
Inhibit 51G-n
51 G Measurement
General Pickup
51G-n
Gn 51G- n Setting
Gn 51G- n Charact
Gn 51G- n Time Mult
Gn 51G- n Delay (DTL)
Gn 51G- n Reset
En.
Gn 51G- n Follower DTL
Gn 51G- n Min. Op. Time
En.
Pickup
trip
Figure 3-16 Logic Diagram: Measured Time Delayed Earth Fault Element (51G)
Summary of Contents for 7SR105 Rho
Page 1: ...Answers for energy 7SR105 Rho User Manual Motor Protection Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices 2 ...
Page 95: ...7SR105 Rho Technical Manual Chapter 4 Page 2 of 70 2018 Siemens Protection Devices ...
Page 99: ...7SR105 Rho Technical Manual Chapter 4 Page 6 of 70 2018 Siemens Protection Devices ...
Page 127: ...7SR105 Rho Technical Manual Chapter 4 Page 34 of 70 2018 Siemens Protection Devices ...
Page 153: ...7SR105 Rho Technical Manual Chapter 4 Page 60 of 70 2018 Siemens Protection Devices ...
Page 155: ...7SR105 Rho Technical Manual Chapter 4 Page 62 of 70 2018 Siemens Protection Devices ...
Page 157: ...7SR105 Rho Technical Manual Chapter 4 Page 64 of 70 2018 Siemens Protection Devices ...