Code

Type

Sensivity (A)

Tripping delay (s)

Communications

P24622

RGU - 10 RAL

0,03-0,1-0,3-0,5-1-3
by direct adjustment
       

5-10-30 by 

SETUP

INS-SEL-0,02-0,1-0,2-0,3-0,4-0,5-0,75-1
              by direct adjustment

3-5-10 by 

SETUP

No Available

P 2 X X X X 0 0 X

Código
 

Code

Código interno
 

Internal code

Tensión de
alimentación

Power supply

230 V a.c. 

110 V a.c.

0

1

RGU-10 RAL Electronic earth leakage protection relay with self-reclosing system

For instance, RGU-10 RAL supplied by 110 V a.c. 

GENERAL DESCRIPTION

-  Device with programmable differential relay with self-reclosing system. Symbol          in LCD.
-  It has 2 independents outputs by relays. Trip and locked by reclosing.
-  It has 1 input for  external Trip/Reclose. This input is opto - coupled.
-  Mounting in Rail DIN  46277 (EN 50022) or panel 72x72 by mean accessory (M5ZZF1)
-  Associated to a 

WG

/

WGS 

Series external , toroidal current transformer.

-  It must be asociated to CONTACTOR like breaking element.
-  It verifies connection with differential transformer 

WG/WGS

 by means inductive test.

-  Leakage detection and measurement is via calculating its true efective value (TRMS).
-  Display settings values and instant residual current to its accociated units.

  

DESCRIPTION LED AND BUTTONS.

-  Shows equipment status via a display and 2 LED.
-  5 button  equipment setup and setting.
-  2 button  equipment TEST and RESET.

INDICATION BY LED AND DISPLAY.

-  

TRIP RELAY. 

LED and display signals a change 

   of status by changing from green to red.l 
   Display event type messages or values.

 BETWEN RECLOSURES. 

   

The yellow LED is blinking. Red Display shows the

   tripp cause fluctuating with partial reclosures No

 

LOCKED BY RECLOSURES

.      

   The yellow LED is  fixed. The equipment arrives al
   maximun number of reclosures established by the
   self-reclosing sequence. Red display shows the cause.
-  

No OF RECLOSURES. 

By short press on 

PROG

 the display shows the number of reclosures by

   earth leakage faults, partial and total number. The partial number are floating pages. In these 
   pages it can configure the self-reclosing sequence by press 

REC 

button.  

RECLOSING THE EQUIPMENT.

-  BY 

TRIP 

LOCKED BY RECLOSURES

   1.  Automathic (earth leakage fault or manual). Is Shown on display
   2.  Manual reclose by pushing button 

RESET

   3.  External reclose sytem by remote or communications signal. When it forces a trip by  remote 
   signal, only it can reclose by another remote signal.
In the case 2 and 3 the all partial counters of reclosures returns to a zero.

 

RELAY PARAMETERS SETTING 

(

 

t

I

 y std/+ )

d

d

t

d

SETTING TRIP DELAY

The               message   and two   values   appear  on the  screen  after 

  pressing  the

button.  The lowest  value indicates   the current   set value  and the highest  is the 

 t

d    

  values to be configured which are  displayed by pressing

The  selected  value to be  saved  is 

      .  

  displayed by showing the message

 SAVE.

I

I

. . 

d

d

SENSITIVITY SETTING

The same operation as above setting is carried out by pressing 

- SIGNALLING CONTACTS RELAY STATE,  std/+

 . Select the default position of the relay contacts 

  4-5-6 that indicates the situation of locked by reclosures of the device .  In (Std) 4-6 NO  / 4-5 NC 
  and (+) 4-5 NC  / 4-6 NO and  appears the     symbol in display.

- SELF-RECLOSING SYSTEM, REC

.   In   reclosure   partial   numbers   by press  

REC

  button we 

  configure the self-reclosing  sequence  referred  at  the  page which it’s showing us.  By default  is 
  configured  nº1 by  earth leakage protection.

PROG

+

Others MESSAGES by display

SAVE
EXIT
OVR
ERRt

Enter setting values 
Exits setting mode
Value reading off scale
Poor toroidal conection

M98204601-03-20A

P24262001

  PARAMETERS BY 

DIRECT ADJUSTMENT 

-DELAY SETTING
-

SETUP

 ROTATION

-SENSIVITY SETTING 

-CONTACTS SETTING NO/NC

-ENABLE/DISABLE 
 SELF-RECLOSING SYSTEM 

REC

RECLOSE SEQUENCES BY EARTH LEAKAGE CURRENT FAULT 

- Varistor Features
  Maximun Voltage:  275 Va.c.

-Characteristics input remote Trip/Reclose 1-2
  Input using optocoupler
Max. Voltage: 230 Va.c.; 0,7 W

TECHNICAL FEATURES

- Tipo 

Relay type: Electronic class A. High frequency current filtering.

- Reclosing type: Authomatic, RESET button or by cutting power supply.
- Rated power supply voltage

: 230 o 110 Va.c. (+/- 20%)  50/60 Hz, 6 VA

             

:  -10ºC / 50ºC

Operating temperature

:

Connections

2

  

0,127 - 2,082 mm

Permissible cable section:          

  Recommended tightening torque: 0.5-0.6 Nm
  Length of cable to strip:                 7 mm

                                                         

 13-14-15 and 4-5-6.

Switch Output contact features

  

: 6/10 A a.c.

Rated current/Maximum instant current

  

: 250/230 V a.c.

Rated voltage/Maximum switching voltage

  

 AC: 2,500 V·A

Rated load in

  Contacts protected by varistor

REC

REC

RAL

 Maximun DC Load Breaking
 Capacity:
 Maximun opening current

Electrical useful life for AC 
loads: No of cycles

¡ IMPORTANT !

The relay only self-recloses after a trip by earth leakage current fault. The Test (red button) only verifies the relay trips 
the protection. It recloses only by manual pressing RESET button.

REC

REC

  (LOCKED SIGNAL)

(See graph)

(See graph)

Tripping cause

Message display

Test
Remote signal trip/reclose
Earth leakage fault

TESt
EXT
DIF / value

GREEN LED: ON 

- RED LED: TRIPPED BY FAULT
- YELLOW LED: Locked by reclosures (fix)/ Betwen reclosures (blinking)
- RESET Button
- Test Button

- SCREENS / 

SETUP 

R

                                

 

 

With the

button  the submenus are browsed 

PROG

                            and with the        button the  values to  be selected 
                            are displayed

                            Press  

  

PROG

to  enter  the value. The  equipment 

                            configures the  value by  displaying

on 

 “

SAVE

” por 

                            the display and then exits Setting Mode

.

                            

If  the   keypad remains  inactive for a certain time, 

                            the   equipment   automatically exits  Setting Mode 
                            and displays

without changing the setting

 “

EXIT

” 

.

                           - SP t configures the status contact relay, NO/NC:
                                                          13- 15 / 6 - 4
                           - RSTC reinitiates the partial counter. 

Button

FREQ

LIM

SEC.T

Button

   60 Hz

10 s, 30 A

RST.C

   SI

Button 

PROG

   SI

   50 Hz

1 s,   3 A

   NO

   NO

- FREQ

, (

) frecuency (Hz)

50

LIM

,(

), range of values (Id / td)

1s, 3A

SEC. T

,  (

),contacts  status relay

NO

         14-15-16 [NA/NC] trip relay
           4-  5-   6[NA/NC] pre-alarma

RST.C

, (

), 

NO

   Initiates the partials counters.

Default values in 

SETUP

SETUP

 SETTINGS

PROG

SREC    No RECLOSURES                TIME SEQUENCES                             RESET TIME

   0                                                                     DISABLED
   1                      6                                 8, 16, 30, 59, 115 and 224 s                   15 minutes
   2                    30                                 20, 40 s and 5 min. to the end                15 minutes
   3                      8                                 30 s, 1, 2, 3, 4, 5, 6 and 7 min                15 minutes
   4                      6                                 10, 20, 30, 60, 130 and 600 s                 15 minutes
   5                      6                                 2, 4 y 8 min. to the end                           15 minutes
   6                      7                                 30 s, 1, 2, 3, 4, 8 and 16 min                  30 minutes
   7                    10                                 1 min                                                       30 minutes
   8                    10                                 90 s                                                         30 minutes
   9                      8                                 2, 4 y 6 minutes to the rest                     15 minutes
 

10

                    10                                 3 minutes                                                30 minutes

 11                      7                                 2, 4, 8, 16, 32, 32 and 32 minutes          15 minutes

 12                    31                                2, 4 and 6 minutes to the rest                  15 minutes
 13                      6                                8 s                                                            15 minutes
 14                     ...                                  ...                                                             ...