Code
Type
Sensivity (A)
Tripping delay (s)
Communications
P24622
RGU - 10 RAL
0,03-0,1-0,3-0,5-1-3
by direct adjustment
5-10-30 by
SETUP
INS-SEL-0,02-0,1-0,2-0,3-0,4-0,5-0,75-1
by direct adjustment
3-5-10 by
SETUP
No Available
P 2 X X X X 0 0 X
Código
Code
Código interno
Internal code
Tensión de
alimentación
Power supply
230 V a.c.
110 V a.c.
0
1
RGU-10 RAL Electronic earth leakage protection relay with self-reclosing system
For instance, RGU-10 RAL supplied by 110 V a.c.
GENERAL DESCRIPTION
- Device with programmable differential relay with self-reclosing system. Symbol in LCD.
- It has 2 independents outputs by relays. Trip and locked by reclosing.
- It has 1 input for external Trip/Reclose. This input is opto - coupled.
- Mounting in Rail DIN 46277 (EN 50022) or panel 72x72 by mean accessory (M5ZZF1)
- Associated to a
WG
/
WGS
Series external , toroidal current transformer.
- It must be asociated to CONTACTOR like breaking element.
- It verifies connection with differential transformer
WG/WGS
by means inductive test.
- Leakage detection and measurement is via calculating its true efective value (TRMS).
- Display settings values and instant residual current to its accociated units.
DESCRIPTION LED AND BUTTONS.
- Shows equipment status via a display and 2 LED.
- 5 button equipment setup and setting.
- 2 button equipment TEST and RESET.
INDICATION BY LED AND DISPLAY.
-
TRIP RELAY.
LED and display signals a change
of status by changing from green to red.l
Display event type messages or values.
-
BETWEN RECLOSURES.
The yellow LED is blinking. Red Display shows the
tripp cause fluctuating with partial reclosures No
-
LOCKED BY RECLOSURES
.
The yellow LED is fixed. The equipment arrives al
maximun number of reclosures established by the
self-reclosing sequence. Red display shows the cause.
-
No OF RECLOSURES.
By short press on
PROG
the display shows the number of reclosures by
earth leakage faults, partial and total number. The partial number are floating pages. In these
pages it can configure the self-reclosing sequence by press
REC
button.
RECLOSING THE EQUIPMENT.
- BY
TRIP
/
LOCKED BY RECLOSURES
1. Automathic (earth leakage fault or manual). Is Shown on display
2. Manual reclose by pushing button
RESET
3. External reclose sytem by remote or communications signal. When it forces a trip by remote
signal, only it can reclose by another remote signal.
In the case 2 and 3 the all partial counters of reclosures returns to a zero.
RELAY PARAMETERS SETTING
(
t
,
I
y std/+ )
d
d
-
,
t
.
d
SETTING TRIP DELAY
The message and two values appear on the screen after
pressing the
button. The lowest value indicates the current set value and the highest is the
t
d
values to be configured which are displayed by pressing
The selected value to be saved is
.
displayed by showing the message
SAVE.
-
,
I
.
I
. .
d
d
SENSITIVITY SETTING
The same operation as above setting is carried out by pressing
- SIGNALLING CONTACTS RELAY STATE, std/+
. Select the default position of the relay contacts
4-5-6 that indicates the situation of locked by reclosures of the device . In (Std) 4-6 NO / 4-5 NC
and (+) 4-5 NC / 4-6 NO and appears the symbol in display.
- SELF-RECLOSING SYSTEM, REC
. In reclosure partial numbers by press
REC
button we
configure the self-reclosing sequence referred at the page which it’s showing us. By default is
configured nº1 by earth leakage protection.
PROG
+
Others MESSAGES by display
SAVE
EXIT
OVR
ERRt
Enter setting values
Exits setting mode
Value reading off scale
Poor toroidal conection
M98204601-03-20A
P24262001
PARAMETERS BY
DIRECT ADJUSTMENT
-DELAY SETTING
-
SETUP
ROTATION
-SENSIVITY SETTING
-CONTACTS SETTING NO/NC
-ENABLE/DISABLE
SELF-RECLOSING SYSTEM
REC
RECLOSE SEQUENCES BY EARTH LEAKAGE CURRENT FAULT
- Varistor Features
Maximun Voltage: 275 Va.c.
-Characteristics input remote Trip/Reclose 1-2
Input using optocoupler
Max. Voltage: 230 Va.c.; 0,7 W
TECHNICAL FEATURES
- Tipo
Relay type: Electronic class A. High frequency current filtering.
- Reclosing type: Authomatic, RESET button or by cutting power supply.
- Rated power supply voltage
: 230 o 110 Va.c. (+/- 20%) 50/60 Hz, 6 VA
-
: -10ºC / 50ºC
Operating temperature
-
:
Connections
2
0,127 - 2,082 mm
Permissible cable section:
Recommended tightening torque: 0.5-0.6 Nm
Length of cable to strip: 7 mm
-
13-14-15 and 4-5-6.
Switch Output contact features
: 6/10 A a.c.
Rated current/Maximum instant current
: 250/230 V a.c.
Rated voltage/Maximum switching voltage
AC: 2,500 V·A
Rated load in
Contacts protected by varistor
REC
REC
RAL
Maximun DC Load Breaking
Capacity:
Maximun opening current
Electrical useful life for AC
loads: No of cycles
¡ IMPORTANT !
The relay only self-recloses after a trip by earth leakage current fault. The Test (red button) only verifies the relay trips
the protection. It recloses only by manual pressing RESET button.
REC
REC
(LOCKED SIGNAL)
(See graph)
(See graph)
Tripping cause
Message display
Test
Remote signal trip/reclose
Earth leakage fault
TESt
EXT
DIF / value
-
GREEN LED: ON
- RED LED: TRIPPED BY FAULT
- YELLOW LED: Locked by reclosures (fix)/ Betwen reclosures (blinking)
- RESET Button
- Test Button
- SCREENS /
SETUP
R
With the
button the submenus are browsed
PROG
and with the button the values to be selected
are displayed
.
Press
PROG
to enter the value. The equipment
configures the value by displaying
on
“
SAVE
” por
the display and then exits Setting Mode
.
If the keypad remains inactive for a certain time,
the equipment automatically exits Setting Mode
and displays
without changing the setting
“
EXIT
”
.
- SP t configures the status contact relay, NO/NC:
13- 15 / 6 - 4
- RSTC reinitiates the partial counter.
Button
FREQ
LIM
SEC.T
Button
60 Hz
10 s, 30 A
RST.C
SI
Button
PROG
SI
50 Hz
1 s, 3 A
NO
NO
- FREQ
, (
) frecuency (Hz)
50
-
LIM
,(
), range of values (Id / td)
1s, 3A
-
SEC. T
, (
),contacts status relay
NO
14-15-16 [NA/NC] trip relay
4- 5- 6[NA/NC] pre-alarma
-
RST.C
, (
),
NO
Initiates the partials counters.
Default values in
SETUP
SETUP
SETTINGS
PROG
SREC No RECLOSURES TIME SEQUENCES RESET TIME
0 DISABLED
1 6 8, 16, 30, 59, 115 and 224 s 15 minutes
2 30 20, 40 s and 5 min. to the end 15 minutes
3 8 30 s, 1, 2, 3, 4, 5, 6 and 7 min 15 minutes
4 6 10, 20, 30, 60, 130 and 600 s 15 minutes
5 6 2, 4 y 8 min. to the end 15 minutes
6 7 30 s, 1, 2, 3, 4, 8 and 16 min 30 minutes
7 10 1 min 30 minutes
8 10 90 s 30 minutes
9 8 2, 4 y 6 minutes to the rest 15 minutes
10
10 3 minutes 30 minutes
11 7 2, 4, 8, 16, 32, 32 and 32 minutes 15 minutes
12 31 2, 4 and 6 minutes to the rest 15 minutes
13 6 8 s 15 minutes
14 ... ... ...