Page 76
SITRANS LG200 – INSTRUCTION MANUAL
7ML19985KA02
Tr
oubl
esho
ot
ing
Error Messages
Level reading on Dis-
play is stuck at full
scale, loop is stuck at
20.5 mA
Software believes probe is
flooded (level very near top of
probe)
Check actual level. If probe is
not flooded, check for buildup
or obstructions near top of
probe. Select higher dielectric
range. Check for condensation
in probe connection. Add
Blocking Distance.
Level, % Output, and
Loop values all at max-
imum level
Possible configuration issue
with single rod probe
1. Increase Blocking Distance.
2. Increase Dielectric Range.
Level, % Output, and
Loop values all read-
ing high vs. actual
Possible obstruction in tank
affecting single rod probe
1. Increase Dielectric Range
until obstruction is ignored.
2. Relocate probe away from
obstruction.
Level value reading
high when should be
zero
Transmitter loose or discon-
nected from probe
Ensure transmitter connected
securely to probe.
Display message
Action
Comment
OK
None
Normal Operating Mode
Initial
None
Program is initializing, level reading
held at 4 mA setpoint. This is a tran-
sient condition
DryProbe
None
Normal message for dry probe. End of
probe signal is being detected.
EOP Low
End of Probe signal from a
dry probe is out of range
• Ensure probe length is entered
correctly.
• Set transmitter to a lower dielectric
range.
EOP High
End of Probe signal is out of
range
• Ensure probe length is entered
correctly.
• Consult factory.
Lvl < PL
Highest level signal
detected is below Probe
Length
• Ensure probe length is entered
correctly.
EOP < PL
End of Probe signal is
below Probe Length
• Ensure probe length is entered
correctly.
WeakSgnl
None. Signal amplitude is
lower than desired
• Set transmitter to lower dielectric
range
• Increase sensitivity
Symptom
Problem
Corrective Action
Summary of Contents for 7ML1301-1
Page 1: ...Instruction Manual February 2009 LG200 sitrans ...
Page 10: ...Page 6 SITRANS LG200 INSTRUCTION MANUAL 7ML19985KA02 SITRANS LG200 Notes ...
Page 59: ...7ML19985KA02 SITRANS LG200 INSTRUCTION MANUAL Page 55 SIMATIC PDM ...
Page 60: ...Page 56 SITRANS LG200 INSTRUCTION MANUAL 7ML19985KA02 SIMATIC PDM Notes ...
Page 96: ...Page 92 SITRANS LG200 INSTRUCTION MANUAL 7ML19985KA02 Hazardous Installation ...