Wiring
Wiring
Power
Connecting SITRANS LG200
Within the transmitter enclosure, connections are made to the terminal blocks and the
ground connectors. The wiring instructions for the LG200 transmitter depend on the
application:
•
General Purpose or Non-incendive (Class I, Div. 2)
•
Intrinsically Safe
•
Explosion Proof
WARNINGS:
• Installation shall only be performed by qualified personnel and in
accordance with local governing regulations.
• All HART versions of SITRANS LG200 transmitter operate at voltages of
11 to 36 V DC at the device terminals. Higher voltage will damage the
transmitter.
Notes:
• Use shielded twisted pair cable: 0.5 to 1 mm² (AWG 22 to 18).
WARNING: Check the nameplate on your instrument, to verify the
approval rating.
Note:
Use shielded twisted pair cable: 0.5 to 1 mm² (AWG 22 to 18).
WARNING: Explosion hazard. Do not disconnect equipment unless
power has been switched off or the area is known to be non-
hazardous.