Safety Zone Alarm Reset (SZ Alarm Reset)
Clears a latched Safety Zone Fault. (User password)
Threshold (Threshld)
Select threshold type. (User password)
Only select FIXED in applications with low dielectric material over higher dielectric
material where device is reading incorrect level (for example, oil over water.)
In FIXED mode, the device captures the first valid return signal and should be used in
water bottom applications or with bulk solids probes with stainless steel weights.
Interface Threshold (Ifc Threshld)
Applicable only when Ifc, Ifc&Vol selected. Select threshold type for interface level pulse.
(User password)
For interface mode only. Threshold for interface pulse levels. Set to CFD for most common
applications.
Poll Address (Poll Adr)
Enter HART polling address number. (User password)
Trim Level (Trim Lvl)
Enter value to adjust level reading. Used to adjust for mounting/installation effects with
single rod probes. (User password)
Trim 4 mA (Trim 4)
Adjust setting to output exactly 4.0 mA. (User password)
Attach a current meter into the loop. Adjust the trim until the meter reads 4.00 mA. The
value of Trim mA is typically 651 counts, but will vary from unit to unit by about ±25 counts.
Trim 20 mA (Trim 20)
Adjust setting to output exactly 20.0 mA. (User password)
Values
Press Enter to clear a latched Safety Zone alarm.
Values
CFD (Constant Fraction Discriminator)
FIXED (Default)
Values
CFD (Constant Fraction Discriminator) (Default)
FIXED
Values
Range 0 to 15. Enter 0 for single transmitter installation
(enter digit other than 0 for multi-drop applications).
(Default: 0)
Values
Trim Lvl xx.x (Range ±20”) (Default: 0.0 in)
Values
Trim 4 xxxx (Trim 4.0 mA output) (Default: 654)
Values
Trim 20 xxxx (Trim 20.0 mA output) (Default: 3269)
Summary of Contents for 7ML1301-1
Page 1: ...Instruction Manual February 2009 LG200 sitrans ...
Page 10: ...Page 6 SITRANS LG200 INSTRUCTION MANUAL 7ML19985KA02 SITRANS LG200 Notes ...
Page 59: ...7ML19985KA02 SITRANS LG200 INSTRUCTION MANUAL Page 55 SIMATIC PDM ...
Page 60: ...Page 56 SITRANS LG200 INSTRUCTION MANUAL 7ML19985KA02 SIMATIC PDM Notes ...
Page 96: ...Page 92 SITRANS LG200 INSTRUCTION MANUAL 7ML19985KA02 Hazardous Installation ...