Application calls for a 72" NPT coaxial
probe in water with the bottom of the
probe 10" above the bottom of the tank. The
user wants the 4 mA point at 24" and the
20 mA point at 60" as referenced from the
bottom of the probe.
When all measurements are referenced from the bottom of the vessel, the value of Lvl
Ofst should be changed to the distance between the bottom of the probe and the bottom
of the vessel as shown in Example 2.
Example 2 (Lvl Ofst = 10):
Application calls for a 72" NPT coaxial
probe in water with the bottom of the
probe 10" above the bottom of the tank.
The user wants the 4 mA point at 24" and
the 20 mA point at 60" as referenced from
the bottom of the tank.
When the SITRANS LG200 transmitter is mounted in a chamber/bridle, the unit is usually
configured with the 4 mA (0%) point at the lower process connection and the 20 mA
(100%) point at the upper process connection. The span is the center-to-center
Lvl Units: in
PrbModel: 7xA-x
PrbMount: NPT
PrbLn: 72"
Lvl Ofst: 0.0 in
Dielctrc: 10 -100
Set 4mA: 24.0"
Set 20 mA: 60.0"
20 mA
4 mA
10"
24"
60"
20 mA
4 mA
10"
60"
24"
Lvl Units: in
PrbModel: 7xA-x
PrbMount: NPT
PrbLn: 72"
Lvl Ofst: 10.0 in
Dielctrc: 10 -100
Set 4mA: 24.0"
Set 20 mA: 60.0"
Summary of Contents for 7ML1301-1
Page 1: ...Instruction Manual February 2009 LG200 sitrans ...
Page 10: ...Page 6 SITRANS LG200 INSTRUCTION MANUAL 7ML19985KA02 SITRANS LG200 Notes ...
Page 59: ...7ML19985KA02 SITRANS LG200 INSTRUCTION MANUAL Page 55 SIMATIC PDM ...
Page 60: ...Page 56 SITRANS LG200 INSTRUCTION MANUAL 7ML19985KA02 SIMATIC PDM Notes ...
Page 96: ...Page 92 SITRANS LG200 INSTRUCTION MANUAL 7ML19985KA02 Hazardous Installation ...