Commissioning
In the
Message Control
field select the variable PRESET_Message.
The MSG block must then be configured.
For this purpose click the button with the three dots.
The
Message Configuration
dialog box will open.
Configure the following parameters on the
Configuration
tab:
–
Service Type:
Set Attribute Single (see Tab. 16 on page 27)
–
Instance:
1 (as only one device is connected to the control system)
–
Class:
23(h) (Position Sensor Object, see Tab. 4 on page 17)
–
Attribute:
13(h) (Preset Value, see Tab. 19 on page 28)
–
Source Element:
PRESET_Value
–
Source Length:
4
PRESET_Value is the fourth variable added. On executing the example program the
preset value is taken from this variable and written to the attribute 13h of the Position
Sensor Object.