Operating Instructions
Chapter
4
AFS60/AFM60 EtherNet/IP
41
Commissioning
4.3.1
Default delivery status
The AFS60/AFM60 EtherNet/IP is supplied with the following parameters:
code sequence = clockwise
scaling = none
steps per revolution = 32,767 (Basic), 262,144 (Advanced)
total resolution = 134,217,727 (Basic), 1,073,741,823 (Advanced)
preset = 0
velocity measuring unit = turns/min
round axis functionality = not activated
nominator for round axis functionality = 2,048
divisor for round axis functionality = 1
4.3.2
IP address assignment via DHCP
The AFS60/AFM60 EtherNet/IP is set from the factory to obtain the IP address from a
DHCP server.
Start the
BOOTP/DHCP server
(as a rule on the Start menu on your PC/notebook in
Rockwell Software
,
BOOTP-DHCP Server
,
BOOTP-DHCP Server
).
In the program window for the BOOTP/DHCP server the AFS60/AFM60 EtherNet/IP
appears as a bus user with its MAC address, however without an IP address assigned.
The Mod LED on the AFS60/AFM60 EtherNet/IP flashes green (the encoder does not yet
have an IP address).
Open the encoder in the BOOTP/DHCP server by double-clicking.
In the
IP Address
field type a valid, spare address and click
OK
.
Fig. 17: MAC address in the
BOOTP/DHCP server
Green
Fig. 18: Entry of the IP
address in the BOOTP/DHCP
server
8018909/1EH9/2021-12-16
Subject to change without notice
© SICK AG• Germany • All rights reserved