79
F0 Group
:
Basic Function Parameters
(
total 15 items
)
Code
Name
Setting Scope
Min
Unit
Defaulted
Value
Addre
ss
Cha
nge
F0.03
Auxiliaryrefer
ence
frequency
0
:
Invalid
1
:
Digital setting,up/down
key
(
Initial value F0.05
)
2
:
Digital setting
,
terminal
UP/DN
(
Initial value
F0.05
)
3
:
Serial port setting
(
Initial value F0.05
)
4
:
Reserved
5
:
AI
6
:
Reserved
7
:
Reserved
8
:
-AI
9
:
Reserved
10
:
Reserved
11
:
AI-5v
12
:
Reserved
13
:
Panel potentionmeter
setting
1
0
003H
○
F0.04
Keypad digital
setting
Low limit frequency
~
upper limit frequency
0.01Hz
50.00Hz
004H
○
F0.05
Digital
auxiliary
frequency
0.0
~
650.00Hz
0.01Hz
0.00Hz
005H
○
F0.06
Base
frequency
0.0
~
650.00Hz
0.01Hz
50.00Hz
006H
×
F0.07
Upper limit of
freq.
Low limit freqenc
~
Max
output frequency
0.01Hz
50.00Hz
007H
×
F0.08
Lowerlimit of
freq.
0.00Hz~upper limit
frequency
0.01Hz
0.00Hz
008H
×