F7.16 Close-loop regulation characteristics
Range
:
0
、
1
【
0
】
0
:
Positive logic
Set F7.16 to 0 if the motor speed is required to increase with the
reference.
1
:
Negative logic
Set F7.16 to 1 if the motor speed is required to decrease with the
increase of the reference.
F7.17~F7.28 Reserved
Reserved
F7.29 PID feedback break line detection
Range
:
0.0
~
80.0%
【
0.00%
】
F7.30 PID feedback break line detection time
Range
:
0.0
~
999.9s
【
0.00s
】
If set F7.29 to 0.0%, no feedback break line detection
Feedback break line detection threshold is a percentage of the full
feedback.
If PID feedback signal is less than F7.29 and last more than setting time
of F7.30, feedback break line alarm will appears.
Note:
Please set F7.29 reasonabely, if not, will cause unnecessary downtime.
6.9
MS parameters
(
F8
)
F8.00 MS freq. 1
Range: lower limit
~
upper limit
【
5.00Hz
】
F8.01 MS freq. 2
Range: lower limit
~
upper limit
【
10.00Hz
】
F8.02 MS freq. 3
Range: lower limit
~
upper limit
【
20.00Hz
】
F8.03 MS freq. 4
Range: lower limit
~
upper limit
【
30.00Hz
】
F8.04 MS freq. 5
Range: lower limit
~
upper limit
【
40.00Hz
】
F8.05 MS freq. 6
Range: lower limit
~
upper limit
【
45.00Hz
】
F8.06 MS freq. 7
Range: lower limit
~
upper limit
【
50.00Hz
】
F8.07~F8.14
MS freq.
8~ 15
Range: lower limit
~
upper limit
【
50.00Hz
】
F7.31~F7.33 Reserved
Reserved