41
SB1
:
Stop button
;
SB2
:
Run button
Terminal Xi is the multi-function input terminal of X1~X5. For this case,
the corresponding parameter should be set at 16 (3-wire operation).
F5.09~F5.11Reserved
Reserved
F5.12 Filter constant
Range
:
0.01
~
50.00s
【
0.50s
】
F5.13 Reserved
Reserved
F5.14 Ratio of Min. input of curve 1
Range
:
0.0
%~
F5.16
【
2.0
%】
F5.15 Frequency corresponds to min. input
of curve 1
Range
:
0.0
~
F0.09
【
0.00Hz
】
F5.16 Ratio of Max. input of curve1
Range
:
F5.14
~
100.0
%【
100.0
%】
F5.17 Frequency corresponds to max. input
of curve 1
Range
:
0.0
~
F0.09
【
50.00Hz
】
F5.18~F5.21Reserved
Reserved
6.7
Output terminal control parameters
(
F6
)
F6.00 Open collector output terminal Y1
Range
:
0
~
19
【
0
】
F6.01 Reserved
Reserved
F6.02 Relay 1 output function
Range
:
0
~
19
【
16
】
F6.03 Reserved
Reserved
Refer to section 3.3.2 for the output characteristics of Y1 and the relay’s
output terminal. Table 6-8 shows the functions of the above 3 terminals.
Note that one function can be selected repeatedly.
Table 6-8 Parameter Setting and Function of Output Terminals
Setting
Function
Setting
Function
0
Inverter running signal
(
RUN
)
1
Frequency arrival signal
(
FAR
)
2
Frequency detection
threshold
(
FDT1
)
3 Reserved
4 Reserved 5
Low voltage lock-up signal
(
LU
)