MS terminals
27
:
Terminal control mode is enabled
When this terminal function is enabled, the operating command is input
through this terminal forcibly. The inverter will be controlled in the
previous mode if FWD/REV terminal function is disabled.
28
~
29
:
Control mode selection X1~X2
Table 6-6 Control Mode Selection
X2
X1
Control mode
OFF OFF
None
OFF ON LED
keypad
ON OFF Terminal
ON ON Serial
port
The selection of control mode is realized by the combination of ON/OFF
state of any two of X1~X5. In the above table, you should set F5.00=28,
F5.01=29.
30~34: Reserved
35: External Stop command
This Stop command is valid to all control modes. When this function is
enabled, the inverter will stop as specified F2.08.
36
:
Reserved
37: Prohibit inverter from operating
If this function is enabled, the inverter that is operating will coast to stop
and the inverter ready to run will be prohibited to start. This function is
mainly used as safety protection.
38
:
Reserved
39
:
Reserved
40: Clear the setting of auxiliary reference frequency