52
Ten: stop frequency processing
0: keep the auxiliary frequency after downtime
1: setting frequency reset after downtime
Hundred: auxiliary frequency superposition of polarity
0: Positive polarity
Sum of main frequency and of auxiliary frequency is defined as set
frequency
1: Negative polarity
D-value of main frequency and of auxiliary frequency is defined as set
frequency
F9.19~F9.21 Reserved
Reserved
F9.22 Cooling fan
Range
:
0
、
1
【
0
】
0
:
Auto-stop mode
The cooling fan keeps running during operation. After the inverter stops
for 3minutes, the cooling fan will continue to run or stop according to
the module temperature.
1
:
Cooling fan keeps running upon power on.
F9.30=0, not auto restart.
In fact, whether to auto restart depends on F9.30, inverter’s state at
power failure and control mode. Refer to Table 6-14.
F9.23~F9.29 Reserved
Reserved
F9.30 Conditions of restart
after power failure
Range
:
0
、
1
【
0
】