28
function. You may input the values on the motor’s nameplate correctly
(F1.01~F1.03);
5
.
If the auto-tuning function is unavailable and there is motor’s
parameters on the nameplate, you should input the values correctly
(F1.01~F1.03), and then input the calculated values (F1.04~F1.08).
Please set the parameters correctly;
6
.
If auto-tuning is not successful, the inverter alarms and displays fault
F.tU.
6.3
Start/Brake Parameter
(
F2
)
F2.00 Reserved
Reserved
F2.01 Start frequency
Range
:
0.20
~
60.00Hz
【
0.50Hz
】
F2.02 Start frequency hold
time
Range
:
0.0
~
10.0s
【
0.0s
】
Start frequency refers the frequency at which the inverter starts, as
shown in Figure 6-9 as f
S.
Start frequency hold time refers the time
within which the inverter runs at start frequency during start up, as
shown in Figure 6-9 t
1:
Figure 6-9 Relation of Start Freq. and Start Time
Note
:
The start frequency is not limited by lower limit of the frequency.