24
F0.06 Base
frequency
Range
:
0.00
~
650.00Hz
【
50.00Hz
】
F0.07 Upper limit of
freq.
Range
:
Upper limit
~
Max output freq.
【
50.00Hz
】
F0.08 Lower limit of
freq
Range
:
0
~
Upper limit of freq.
【
0.00Hz
】
F0.09 Max output
frequency
Range
:
Max{50.00, F0.12 upper limit of
frequency}
~
650.00H
【
50.00Hz
】
F0.10 Max output
voltage
Range
:
1
~
480V
【
Inverter’s rated
】
Figure 6-6 Characteristic parameters definition
The max frequency refers to the allowed max output frequency of the
inverter. Refer to the f
max
in Figure 6-6;
Base frequency normally corresponds with the rated frequency of the
motor. It is the Min frequency when the inverter outputs the highest
voltage, as shown in Figure 6-6 as f
b
Max output voltage is the inverter’s output voltage when the inverter
outputs base frequency, as shown in Figure 6-6 as V
max
. This
f
max
Output voltage
f
b
f
H
f
L
V
max