108
If the operation fails, error code and exception code will be responded.
The error code is “function code + 0x80”, exception code refers to the
previous description.
Inverter control parameters can accomplish functions such as start, stop,
operation frequency, etc. By retrieving the inverter state parameter,
users can obtain operation parameters such as frequency, output current
and output torque. Specific frequency converter control parameters and
status parameters enumerated below
:
Inverter control parameter index
Register address
Name of parameter
Power-do
wn save?
0x3200
Control command word
No
0x3201 Main
setting
Yes
0x3202
Operation frequency setting
Yes
0x3203
Digital closed-loop given
Yes
0x3204 Reserved
No
0x3205
Analog output AO setting
No
0x3206 Reserved
No
0x3207
Digital output Y1 setting
No
0x3208
Set the frequency ratio
No
0x3209
Virtual terminal control seting
No
0x320A
Set acceleration time 1
Yes
0x320B
Set deceleration time 1
Yes
SINUS VEGA inverter state parameter index
Register
address
Parameter name
0x3300
Running status word 1
0x3301
The practical operation value of the current main
setting
0x3302
Slave drive model
0x3303 Inverter
type
0x3304 Software
version
0x3305 Present
running
frequency
0x3306 Output
current
0x3307 Output
Voltage