F7 Group
:
Process Closloop PID Parameters
(
Toal 34
)
Code
Name
Setting Scope
Min
Unit
Default
ed
Value
Address
Cha
nge
F7.00
Close-loop PID
control
0
:
Non Closeloop PID
control run
1
:
Closeloop PID control
run
1 0 700H ×
F7.01
Reference input
method
0:Digital setting(F7.05
value)
1
:
Reserved
2
:
Reserved
3: LED keypad
potentiometer given
4
:
Reserved
1 0 701H
○
F7.02 Reserved
-
- - 702H
*
F7.03 Input
filter 0.01
~
50.00s
0.01s
0.5s 703H
○
F7.04 Feedback
filter
0.01
~
50.00s
0.01s
0.5s 704H
○
F7.05
Digital
referenceinput
0.00
~
10.00V
0.01 0.00 705H
○
F7.06 Reserved
-
-
- 706H *
F7.07 Reserved
-
-
- 707H *
F7.08 Min
input 0.0%
~
F7.10
0.1%
0.0 708H
○
F7.09
Feedback of
Min input
0.0
~
100.0%
0.1%
0.0% 709H
○
F7.10 Max
input F7.08
~
100.0%
0.1%
100.0% 70AH
○
F7.11
Feedback of
Max input
0.0
~
100.0%
0.1%
100.0% 70BH
○
F7.12
Proportional
gain Kp
0.000
~
9.999
0.001
0.050 70CH
○
F7.13
Integral gain Ki 0.000
~
9.999
0.001
0.050 70DH
○
F7.14
Sampling cycle
Ts
0.01
~
50.00s
0.01s
0.50s 70EH
○
F7.15 Error
limit 0.0
~
20.0%
0.1%
2.0% 70FH
○
F7.16
Closed-loop
regulation
characteristics
0
:
Positive logic
1
:
Negative logic
1 0 710H
×