78
9
Parameter profiles
“
○
”
:
Indicate the set value of the parameter can be changed when
the inverter is in stop status or running status.
“×”
:
Indicate the set value of the parameter cannot be changed
when the inverter is in running status.
“*”
:
It represents the value of this parameter is the actually
measured value and cannot be changed.
“-”: It indicates that the parameter is "Factory default parameter"
set only by the manufacturer and forbidden for users to change.
“Address” is the address of MODBUS protocol register
F0 Group
:
Basic Function Parameters
(
total 15 items
)
Code
Name
Setting Scope
Min
Unit
Defaulted
Value
Addre
ss
Cha
nge
F0.00
Command
channel
0:Keypad command
channel
1:Termminal control
2:Serial communication
port control
1
0
000H
○
F0.01 Reserved
-
-
-
001H
*
F0.02
Frequency
source setting
0
:
Digital setting 1
(Up/Down key)
1
:
Digital setting 2
(Terminal UP/DN )
2: Digital setting3
Serial communication port
3
:
Reserved
4
:
AI setting
5
:
Reserved
6
:
Keypad potentionmeter
setting
1
0
002H
○