Table 6-14 Conditions of Restart after Power-on
F9.30
State before
power off
Control mode at power-on
Keypad
Serial port 3-wire terminal 1
、
2 2-wire terminal 1
、
2
None
None
None
None
Yes
0
Stop
0
0
0
0
0
Run
0
0
0
0
0
1
Stop
0
0
0
0
1
Run
1
1
1
0
1
Note
:
1
.
Table 6-14 shows the inverter’s action under different conditions.
“0” means the inverter is ready to start, and “1” means auto start.
2
.
When the control mode is keypad or serial port or 3-wire terminal 1
and 2, there is no RUN command at power on.
3
.
If there is a Stop command, the inverter will not start.
F9.31~F9.33 Reserved
Reserved
F9.34 Terminal filter time
Range
:
0.5~100.0ms
【
7.5ms
】
F9.35 Current count value
Range
:
0~65535
【
0
】
Terminal filter time: can increase P9.34 properly, improve the
anti-interference ability of the X input terminals.Terminal filter, the
longer terminal action delay time is longer.
The current count value: built-in counter for input pulse count, the value
can be modified on-line, this value can be saved when power off.
F9.36 Under-voltage point set
Range
:
75.0%
~
135.0%
【
90%
】