113
address
Function
Code
Register
address
Register
number or read
number of
bytes
Register
content
Checksum
Request 0x01 0x03 0x3306
0x0001
none 0x6B4F
Response 0x01
0x03 none
0x02
0x012C 0xB809
10.5
The scaling rule of Inverter
A
)
The calibration of frequency is 1:100
To make inverter running at 50 hz, the main setting should be 0 x1388
(
5000
)
.
B
)
The calibration of time is 1:10
To make the acceleration time to be 30s, the function code setting
should be 0x012c
(
300
)
.
C
)
The calibration of current is1:10
If the feedback current of inverter is 0x012c
,
the current of the inverter
is 30A.
D
)
Output power is its absolute value.
E
)
Other issues(such as input and output terminals, etc.), please refer to
the user manual.