4.3.5 Room linkage setup
Fig 4- 42 Room linkage setup
For room linkage, start room number and end room number at a certain floor can be selected
by drop-down box, which means: When detector or module of any specified type at all rooms with
a number between start number and end number at the floor gives an alarm, all modules listed in
the output result list will be activated.
4.3.6 Complex linkage setup
Fig 4- 43 Complex c&e setup window
The complex linkage setup differs greatly with the above linkage relations and the specific
addresses of 1-5 detectors or modules can be set in the condition column. The meaning of
combined linkage:
start all modules listed at the result list when all the set detectors or
modules generate alarms.
Note:
The host number can be set in the condition column, which means detector or modules
participating in the compound operation may come from any host in the networking system!
Less than 5 detectors or modules can be set in the condition column and the remaining input
columns must be kept empty if the number is less than 5. If the user requires more than 5
detectors or modules, dummy modules can be used for setup.